Combination wave pulse 1, 2/50 - 8/20 μs (Hybrid-Surge pulse)
Pulse conforms to IEC/EN 61000-4-5
Parameter |
Value |
Pulse voltage (open circuit): |
±200 V to 6.6 kV (in 1 V steps) |
Pulse current (short circuit): |
±100 A to 3.3 kA |
Impedance: |
2/12 Ω |
Polarity: |
positive / negative / alternate |
Pulse repetition: |
10 s* up to 9’999 s (in 1 s steps) |
Test duration: |
1 to 99’999 pulses, continuous |
Phase synchronization: |
asynchronous, synchronous 0 to 359º (in 1º steps) |
Coupling: |
ANSI / IEC / external |
Ring wave 0.5 µs /100 kHz
Pulse conforms to IEC/EN 61000-4-12 and ANSI (IEEE) C62.41
Parameter |
Value |
Pulse voltage (open circuit): |
± 200 V to 6.6 kV (in 1 V steps) |
Pulse current (short circuit): |
±16.6 to ±550 A, ±10% ±6.6 to ±220 A, ±10% ±1 to ±33 A, ±10% |
Impedance: |
12/30 Ω |
Polarity: |
positive / negative / alternate |
Pulse repetition: |
10 s* up to 9’999 s (in 1 s steps) |
Test duration: |
1 to 99’999 pulses, continuous |
Phase synchronization: |
asynchronous, synchronous 0 to 359º (in 1º steps) |
Coupling: |
ANSI / IEC / external |
Burst (EFT) 5/50 ns
Pulse conforms to IEC/EN 61000-4-4
Parameter |
Value |
Pulse amplitude: |
±200 V to 4.8 kV (in 1 V steps) - open circuit ±100 V to 2.4 kV (50 Ω matching system) |
Burst frequency: |
100 Hz to 1000 kHz |
Polarity: |
positive / negative / alternate |
Repetition time: |
10 ms to 9'999 ms |
Burst time: |
0.01 ms to 9'999 ms, single pulse |
Test duration: |
1 s to 9’999s, 1 min to 1600 min, endless |
Phase synchonization: |
asynchronous, synchronous 0 to 359º (in 1º steps) |
Coupling: |
internal / external |
Dips, Interrupts & Variations
Conforms to IEC/EN 61000-4-11, IEC/EN 61000-4-29
Parameter |
Value |
Dips & Interrupts: |
From EUT voltage input to 0 V, 0% (1) |
Uvar with optional variac: |
depending on model (VAR 3005A) |
Uvar with step transformer: |
0, 40, 70, 80% (INA 650xA) |
Peak inrush current capability: |
> 500 A (at 230 V) |
Switching times: |
1 to 5 μs (100 Ω load) |
Event time (T-Event): |
20 µs to 9999 s, 0.5 to 9’999 cycles |
Repetition time: |
10 ms to 9’999 ms, 1 to 9’999 s |
Test duration: |
1 to 99’999 events, endless |
Phase synchronization: |
asynchronous, synchronous 0 to 359º (in 1º steps) |
Variation test (with VAR 3005A only)
conforms to IEC/EN 61000-4-11
Parameter |
Value |
Uvar with optional variac: |
up to 265 V (in 1 V steps) or up to 115% Uin (in 1% steps) |
Decreasing time Td: |
1 ms to 9.999 ms, 0.5 to 9999 cycles, abrupt |
Time at reduced voltage Ts: |
1 ms to 9.999 ms, 0.5 to 9999 cycles, |
Increasing time Ti: |
1 ms to 9.999 ms, 0.5 to 9999 cycles, |
Repetition time: |
1 s to 9’999 s |
Events: |
1 to 99’999 |
Pulsed magnetic field in conjunction with 702A
conforms to IEC/EN 61000-4-9
Parameter |
Value |
Field: |
100 to 1200 A/m |
Polarity: |
positive / negative / alternate |
Repetition time: |
10 s to 9999s (in 1 s steps) |
Impedance: |
2 Ω |
Coil / impedance factor: |
0.01 to 100.00 |
Test duration: |
1 to 9’999 pulses, endless |
Phase synchronization: |
asynchronous, synchronous 0 to 359º (in 1º steps) |
Power magnetic field in conjunction with MFT 30 or MFO 6501 and MFC 30
& MFC 300
conforms to IEC/EN 61000-4-8
Field: |
1 to max. 40 A/m (in 1 A/m steps) |
Frequency: |
50/60 Hz |
Coil factor: |
0.01 to 99.99 |
Test duration: |
1 to 9’999 pulses, continuous |